Engineering resource

Cable ladder load ratings

Published safe working loads for tested Array Metal cable ladder, tray and wire-mesh systems, stated by support span. Each rating includes the safety factor used by its test programme.

IEC 61537NEMA VE1-2009SIRIM-tested programme

Published test data

Values are uniformly distributed safe working loads in kg/m. Select the row for the rail height and the column matching the support span.

Cable Ladder

AML Series

NEMA VE1 · Hot-Dip Galvanized (HDG) · Safety factor ×1.5

NEMA VE1-2009
ModelLoading depthThicknessSWL @ 3 m (kg/m)SWL @ 4.5 m (kg/m)SWL @ 6 m (kg/m)NEMA class
AML10075 mm1.5 / 2 mm1928548NEMA 20AA
AML125100 mm1.5 / 2 mm480213120NEMA 20B
AML150125 mm1.5 / 2 mm468208117NEMA 20B

Rating basis. SWL = Destructive load ÷ 1.5 (NEMA VE1-2009). Available lengths: 3 m and 6 m. Deflection limit: L/100 at SWL.

Cable Ladder

AML Series

IEC 61537:2006, Test Type 2 · Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThicknessSWL @ 3 m (kg/m)SWL @ 4.5 m (kg/m)SWL @ 6 m (kg/m)NEMA class
AML10075 mm1.5 / 2 mm1566939NEMA 20AA
AML125100 mm1.5 / 2 mm456203114NEMA 20B
AML150125 mm1.5 / 2 mm504224126NEMA 20B

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006, Test Type 2). Available lengths: 3 m and 6 m.

Cable Ladder

APO Series

NEMA VE1 · Hot-Dip Galvanized (HDG) · Safety factor ×1.5

SIRIM / NEMA VE1-2009
ModelLoading depthThicknessSWL @ 3 m (kg/m)SWL @ 4.5 m (kg/m)SWL @ 6 m (kg/m)NEMA class
APO10075 mm1.5 / 2 mm1928548NEMA 20AA
APO125100 mm1.5 / 2 mm416185104NEMA 20A
APO150125 mm1.5 / 2 mm540240135NEMA 20B

Rating basis. SWL = Destructive load ÷ 1.5 (NEMA VE1-2009). Test certificate reference: SIRIM-NEMA VE1-2009. Available lengths: 3 m and 6 m.

Cable Ladder

APO Series

IEC 61537:2006, Test Type 2 · Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThicknessSWL @ 3 m (kg/m)SWL @ 4.5 m (kg/m)SWL @ 6 m (kg/m)NEMA class
APO10075 mm1.5 / 2 mm22810157NEMA 20AA
APO125100 mm1.5 / 2 mm408181102NEMA 20A
APO150125 mm1.5 / 2 mm452240113NEMA 20B

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006, Test Type 2). Available lengths: 3 m and 6 m.

Cable Ladder

ACD Series

IEC 61537:2006, Test Type 2 · Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThicknessSWL @ 3 m (kg/m)SWL @ 4.5 m (kg/m)SWL @ 6 m (kg/m)NEMA class
ACD10075 mm1.5 mm (tested)23910660NEMA 20AA
ACD125100 mm1.5 / 2 mm560249140NEMA 20B
ACD150125 mm1.5 / 2 mm579257145NEMA 20B

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006). Breaking load confirmed ≥ 1.7 × SWL by test. Certificate ref: 2018MA0594-ACD-IEC61537. Available lengths: 3 m and 6 m. Full test certificate available on request.

Cable Ladder

AZL Series

IEC 61537:2006, Test Type 2 · Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThicknessSWL @ 3 m (kg/m)SWL @ 4.5 m (kg/m)SWL @ 6 m (kg/m)NEMA class
AZL10075 mm1.5 / 2 mm2089252NEMA 20AA
AZL125100 mm1.5 / 2 mm408181102NEMA 20A
AZL150125 mm1.5 / 2 mm536238134NEMA 20B

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006, Test Type 2). Available lengths: 3 m and 6 m.

Cable Tray

ART / AMT Series

NEMA VE1 · Hot-Dip Galvanized (HDG) · Safety factor ×1.5

NEMA VE1-2009
ModelLoading depthThicknessSWL @ 1.5 m (kg/m)SWL @ 2 m (kg/m)SWL @ 3 m (kg/m)NEMA class
ART5050 mm1.5 / 2 mm484272121NEMA 20AA
AMT100100 mm1.5 / 2 mm716403179NEMA 20B

Rating basis. SWL = Destructive load ÷ 1.5 (NEMA VE1-2009). Available lengths: 3 m and 6 m. Deflection limit: L/100 at SWL.

Cable Tray

ART / AMT Series

IEC 61537:2006, Test Type 2 · Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThicknessSWL @ 1.5 m (kg/m)SWL @ 2 m (kg/m)SWL @ 3 m (kg/m)NEMA class
ART5050 mm1.5 / 2 mm39222198NEMA 10A
AMT100100 mm1.5 / 2 mm1076605269NEMA 10A

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006, Test Type 2). Available lengths: 3 m and 6 m.

Wire Mesh Tray

AWT Series

NEMA VE1 · Hot-Dip Galvanized (HDG) · Safety factor ×1.5

NEMA VE1
ModelLoading depthThicknessSWL @ 1.5 m (kg/m)SWL @ 2 m (kg/m)SWL @ 3 m (kg/m)NEMA class
AWT5050 mm4.5 mm wire885022NEMA 5A
AWT100100 mm4.5 mm wire965424NEMA 8AA
AWT100100 mm5.9 mm wire24814062NEMA 10AA

Rating basis. SWL = Destructive load ÷ 1.5 (NEMA VE1). AWT100 has separate ratings for 4.5 mm and 5.9 mm wire diameters.

Methodology

Test conditions and safety factors

NEMA VE1-2009

APO · AML · ART · AMT · AWT series

Test type
Single-span, uniformly distributed load
Safety factor
×1.5
SWL definition
Destructive load ÷ 1.5
Deflection limit
L/100 at SWL
Load classification
5A, 8AA, 10AA, 10A, 20AA, 20A, 20B (increasing capacity)
Test body
SIRIM (Malaysia)

IEC 61537:2006

ACD · AZL · AML · APO · ART · AMT series

Test type
Single-span, uniformly distributed load
Safety factor
×1.7
SWL definition
Breaking load ÷ 1.7
Deflection limit
L/100 at SWL
Breaking load
Confirmed ≥ 1.7 × SWL by test
Certificate ref
2018MA0594-ACD-IEC61537
Chat on WhatsApp