Engineering resource

Cable Ladder & Tray Selector

Enter a load and a support spacing to see every tested Array Metal ladder, tray and wire-mesh model that carries it. The full published safe working loads follow below.

  • IEC 61537:2006
  • NEMA VE1-2009
  • Tested by SIRIM

Cable Ladder

AML Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.5

NEMA VE1-2009
ModelLoading depthThickness3 mSWL kg/m4.5 mSWL kg/m6 mSWL kg/mNEMA class
AML10075 mm1.5 / 2 mm192854820AA
AML125100 mm1.5 / 2 mm48021312020B
AML150125 mm1.5 / 2 mm46820811720B

Rating basis. SWL = Destructive load ÷ 1.5 (NEMA VE1-2009). Available lengths: 3 m and 6 m. Deflection limit: L/100 at SWL.

Cable Ladder

AML Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThickness3 mSWL kg/m4.5 mSWL kg/m6 mSWL kg/m
AML10075 mm1.5 / 2 mm1566939
AML125100 mm1.5 / 2 mm456203114
AML150125 mm1.5 / 2 mm504224126

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006, Test Type 2). Available lengths: 3 m and 6 m.

Cable Ladder

APO Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.5

SIRIM / NEMA VE1-2009
ModelLoading depthThickness3 mSWL kg/m4.5 mSWL kg/m6 mSWL kg/mNEMA class
APO10075 mm1.5 / 2 mm192854820AA
APO125100 mm1.5 / 2 mm41618510420A
APO150125 mm1.5 / 2 mm54024013520B

Rating basis. SWL = Destructive load ÷ 1.5 (NEMA VE1-2009). Test certificate reference: SIRIM-NEMA VE1-2009. Available lengths: 3 m and 6 m.

Cable Ladder

APO Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThickness3 mSWL kg/m4.5 mSWL kg/m6 mSWL kg/m
APO10075 mm1.5 / 2 mm22810157
APO125100 mm1.5 / 2 mm408181102
APO150125 mm1.5 / 2 mm452201113

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006, Test Type 2). Available lengths: 3 m and 6 m.

Cable Ladder

ACD Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThickness3 mSWL kg/m4.5 mSWL kg/m6 mSWL kg/m
ACD10075 mm1.5 mm (tested)23910660
ACD125100 mm1.5 / 2 mm560249140
ACD150125 mm1.5 / 2 mm579257145

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006). Breaking load confirmed ≥ 1.7 × SWL by test. Certificate ref: 2018MA0594-ACD-IEC61537. Available lengths: 3 m and 6 m. Full test certificate available on request.

Cable Ladder

AZL Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThickness3 mSWL kg/m4.5 mSWL kg/m6 mSWL kg/m
AZL10075 mm1.5 / 2 mm2089252
AZL125100 mm1.5 / 2 mm408181102
AZL150125 mm1.5 / 2 mm536238134

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006, Test Type 2). Available lengths: 3 m and 6 m.

Cable Tray

ART / AMT Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.5

NEMA VE1-2009
ModelLoading depthThickness1.5 mSWL kg/m2 mSWL kg/m3 mSWL kg/mNEMA class
ART5050 mm1.5 / 2 mm48427212120AA
AMT100100 mm1.5 / 2 mm71640317920B

Rating basis. SWL = Destructive load ÷ 1.5 (NEMA VE1-2009). Available lengths: 3 m and 6 m. Deflection limit: L/100 at SWL.

Cable Tray

ART / AMT Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.7

IEC 61537:2006
ModelLoading depthThickness1.5 mSWL kg/m2 mSWL kg/m3 mSWL kg/m
ART5050 mm1.5 / 2 mm39222198
AMT100100 mm1.5 / 2 mm1076605269

Rating basis. SWL = Breaking load ÷ 1.7 (IEC 61537:2006, Test Type 2). Available lengths: 3 m and 6 m.

Wire Mesh Tray

AWT Series

Hot-Dip Galvanized (HDG) · Safety factor ×1.5

NEMA VE1
ModelLoading depthThickness1.5 mSWL kg/m2 mSWL kg/m3 mSWL kg/mNEMA class
AWT5050 mm4.5 mm wire8850225A
AWT100100 mm4.5 mm wire9654248AA
AWT100100 mm5.9 mm wire2481406210AA

Rating basis. SWL = Destructive load ÷ 1.5 (NEMA VE1). AWT100 has separate ratings for 4.5 mm and 5.9 mm wire diameters.

Methodology

Test conditions and safety factors

Every figure on this page is a safe working load with the standard’s safety factor already applied. Loading depth is the internal usable cable fill depth of the side rail.

NEMA VE1-2009

APO · AML · ART · AMT · AWT series

Test type
Single-span, uniformly distributed load
Safety factor
×1.5
SWL definition
Destructive load ÷ 1.5
Deflection limit
L/100 at SWL
Load classification
5A, 8AA, 10AA, 10A, 20AA, 20A, 20B (increasing capacity)
Test body
SIRIM (Malaysia)

IEC 61537:2006

ACD · AZL · AML · APO · ART · AMT series

Test type
Single-span, uniformly distributed load
Safety factor
×1.7
SWL definition
Breaking load ÷ 1.7
Deflection limit
L/100 at SWL
Breaking load
Confirmed ≥ 1.7 × SWL by test
Certificate ref
2018MA0594-ACD-IEC61537

NEMA classification per NEMA VE1-2009: 20AA < 20A < 20B (increasing capacity).

Need the test certificates?

Test reports and vendor prequalification documents are on the certifications page. For a load case outside these tables, send it to our engineering team.